34211, Type UA – Liquid-Tight Flexible Metal Conduit (LFMC)
Thermoplastic PVC jacket with integral bonding wire 3/8″ through 1-1/4″
Thermoplastic PVC jacket with integral bonding wire 3/8″ through 1-1/4″
Conduit shall be Anaconda SEALTITE® Type UA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8″ thru 1-1/4″. Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8″ thru 4″. Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.
Type
|
UA |
Electrical Trade Size
|
1/2 in
16 mm |
Length
|
200 ft
60.96 m |
Packaging
|
Standard Carton |
Inside Diameter
|
0.622 to 0.642 in
15.799 to 16.307 mm |
Outside Diameter
|
0.822 to 0.840 in
20.879 to 21.336 mm |
Approx. Inside Bend Radius
|
3.5 in
88.9 mm |
Approx. Weight per 100 ft
|
29 lbs
13.15 kg |
Color
|
GRAY |
Optional Colors
|
Black |
Certifications
|

UL Listed & CSA Certified
|
Cross-Reference #
|
LA-11 |
- Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
- Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
- Approved as an equipment grounding conductor in sizes 3/8″ through 1-1/4″ if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8″ and 1/2″ and 60 amps or less for 3/4″ through 1-1/4″.
- Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
- Manufactured in a full range of trade sizes from 3/8″ through 4″.
- Approved for direct burial and in concrete trade sizes 3/8″ through 4″.
- Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.
|
- Article 250.118 (6) Equipment Grounding
- Article 300.22 (D) Information Technology Equipment
- Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
- Article 501.10 (B) (2) Class I Div. 2
- Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
- Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
- Article 620.21 Elevator Wiring Methods
- Article 645.5 (E) (2) Under Raised Floors
|
Where UL Listing is Required and Conduit Grounding is Necessary
Temperature Range: -40ºF to +176ºF (-40ºC to +80ºC) |